Voltage Drop Calculator: Wire Size and Distance Guide

Learn how voltage drops over wire distance and how to choose the right wire size. Essential for solar installations, long runs, and electrical design.

Every wire has resistance, and every meter of wire drops some voltage. For short household runs, this is negligible. But for solar installations, long cable runs, or high-current applications, voltage drop can be the difference between a working system and a failed one.

How Voltage Drop Works

Voltage drop = current × wire resistance. Wire resistance increases with length and decreases with diameter. The formula: V_drop = I × R, where R = resistivity × length ÷ area.

Copper resistivity: 1.68 × 10⁻⁸ Ω·m. For 100 meters of 2.5 mm² copper wire: R = 1.68×10⁻⁸ × 100 ÷ (2.5×10⁻⁶) = 0.672 Ω. At 10A: voltage drop = 10 × 0.672 = 6.72V — significant on a 12V system but negligible on 230V.

Voltage Drop by Application

Solar installations (12–48V): Critical because even small drops represent large percentages. A 1V drop on a 12V system is 8.3% loss. Use thick cables (6–10 mm²) and keep runs short.

Household wiring (120/230V): NEC recommends max 3% drop on branch circuits and 5% total (feeder + branch). For 230V at 20A over 30m: use 4 mm² wire for 2.3% drop.

EV charging (240V, 32–48A): Over long distances (50m+), upsizing wire is essential. A 50m run at 40A needs 10 mm² to stay under 3% drop.

Minimizing Voltage Drop

  • Increase wire size: Doubling cross-section halves the resistance
  • Increase voltage: Same power at double voltage = half current = quarter the power loss
  • Shorten the run: Route cables as directly as possible
  • Use copper over aluminum: Copper has 60% lower resistivity

This is why power transmission lines use extremely high voltages (up to 765 kV) — it dramatically reduces current and therefore reduces I²R losses.

Try the Electric Voltage Converter

Convert between all electric voltage units instantly.

Open Converter

Frequently Asked Questions

What is an acceptable voltage drop?
NEC recommends 3% for individual circuits and 5% total from service entrance to farthest outlet. For sensitive electronics, keep it under 2%.
Does voltage drop waste energy?
Yes. Voltage drop causes power loss as heat in the wires (P = I²R). A 3% voltage drop at 20A means about 17 watts wasted per 100m of 2.5mm² copper wire.
Aluminum or copper wire?
Copper is better for most applications: lower resistance, more durable connections. Aluminum is used for utility-scale and large feeders where cost savings outweigh the need for larger wire size.